CHP-254-2T-3 — CHP
Back to CHP

CHP-254-2T-3

CHP — CENTRIFUGAL

Sound Data

2 records

Dimensions

24 params

Description

CHP Centrifugal single-inlet, high-pressure fans with casing and sheet steel impeller

Fan:

  • Steel sheet casing

  • Impeller with backward-facing blades made from galvanised sheet steel, except models 242-248-254-260 640-645-650 which have a cast aluminium impeller.

Motor:

  • Motors with IE-2 efficiency, except for motors with lower powers than 0.75 kW and single-phase motors.

  • Class F motors, with bearings, IP55 protection.

  • Three-phase 230/400V.-50Hz. (up to 5.5 HP) and 400/690V.-50Hz. (power over 5.5 HP)

  • Max. air temperature to transport: -20°C. + 120°C

Finish:

  • Anticorrosive finish in polyester resin, polymerised at 190°C, after alkaline degreasing and phosphate-free pre-treatment.

On request:

  • Special windings for different voltages

  • Fan designed to transport air up to 250ºC

  • Stainless steel fans

  • ATEX certification, Category 2

Performance curve

Hover the curve to read values
02,0004,0006,00005001,0001,500m³/hPa
Fan curve

Your duty point

Fan limits

Max airflow
1,300 m³/h
Max static pressure
5,305 Pa