Description
FBFT-I 400ºC/2h extraction units with motor and belt-driven inside the plate to work outside fire danger zones. Clean and odourless air at all times
Fan:
-
Galvanised sheet steel structure.
-
Impeller with forward-facing blades made from galvanised sheet steel
-
Approval according to Standard EN 12101-3:2002/AC:2006, with certification No: 0370-CPR-0468
-
Linear air circulation
Motor:
-
Class F insulation, IP55, one-or two-speed depending on the model
-
Three-phase 230/400V.-50Hz. (up to 5.5HP) and 400/690V.-50Hz. (power over 5.5HP).
-
Max. air temperature to transport: S1 Service -20°C + 120ºC for ongoing use, S2 Service 200°C /2h, 300°C /2h and 400°C /2h
Finish:
- Anti-corrosive galvanised sheet steel
On request:
- Fans with vertical outlet
Performance curve
Hover the curve to read values
Fan curve
Your duty point
Fan limits
- Max airflow
- 28,075 m³/h
- Max static pressure
- 695 Pa