XMF-40-4M — XMF
Back to XMF

XMF-40-4M

XMF — AXIAL

Sound Data

2 records

Dimensions

6 params

Description

XMF Mobile fans with possibility of directing airflow.

Fan:

  • Sheet steel tubular casing.

  • Impeller in polyamide 6 reinforced with fibre glass

  • Protection guard against contacts, in accordance with standard UNE 100250, on both sides

  • Connection box with start-stop switch that can be rearmed manually to avoid switching the fan on accidentally (ISO 12100-2)

  • Airflow direction from motor to impeller

Motor:

  • Single-phase two-speed motors with IE-2 efficiency, except lower powers 0.75 kW.

  • Class F motors, with ball bearings and IP55 protection, except single-phase versions from size 35 to size 56, IP54 protection.

  • Single-phase 230V.-50Hz., and three-phase 230/400V.-50Hz.

  • Working temperature: -25°C. + 50°C

Finish:

  • Anticorrosive finish in polyester resin, polymerised at 190°C, after alkaline degreasing and phosphate-free pre-treatment.

On request:

  • Airflow direction from impeller to motor

  • 100% reversible impellers.

  • Special windings for different voltages

  • ATEX certification, Category 2

Sound Spectrum Analysis

2 measurements

Sound Power dB(A)

Total: 76 LWA
0204060LWA2963461255825066500711k712k674k608kFrequency (Hz)

Sound Pressure dB(A)

Total: 58 LPA
02040LPA1163281254025048500531k532k494k428kFrequency (Hz)
TypeUnit63 Hz125 Hz250 Hz500 Hz1k Hz2k Hz4k Hz8k HzTotal
Sound Power dB(A)LWA29.046.058.066.071.071.067.060.076
Sound Pressure dB(A)LPA11.028.040.048.053.053.049.042.058