XCT-63-4T-2 — XCT
Back to XCT

XCT-63-4T-2

XCT — AXIAL

Sound Data

2 records

Dimensions

7 params

Description

XCT Short casing axial fans for working inside fire danger zones. XCT/ATEX: with ATEX certification, category 3 Ex II3G. In accordance with Spanish Low Voltage Regulation Itc 29 ATEX for Zone 2 rated car parks.

Fan:

  • Sheet steel short casing. XCT/ATEX: with aluminium strip in the impeller area in accordance with Standard EN-14986:2005.

  • Turn able cast aluminium impellers.

  • Approval according to Standard EN-12101-3-2002.

  • Airflow direction from motor to impeller.

Motor:

  • Class H motors, ongoing use S1 and emergency use S2, with ball bearings, IP55 protection, and one or two speeds depending on the model.

  • Three-phase 230/400V.-50Hz. (up to 4 HP) and 400/690V.-50Hz. (power over 4 HP)

  • Max. temperature of air for transport: S1 Service -20ºC+ 40ºC for ongoing use, S2 Service 200°C /2h, 300°C /2h, 400°C /2h

Finish:

  • Anticorrosive finish in polyester resin, polymerised at 190ºC, after alkaline degreasing and phosphate-free pre-treatment.

On request:

  • Long casing fans with inspection hatch

  • 100% reversible impellers.

Performance curve

Hover the curve to read values
0100200300400010,00020,00030,000m³/hPa
Fan curve

Your duty point

Fan limits

Max airflow
24,239 m³/h
Max static pressure
305 Pa